LX-5162 Addressable Rate of Rise Fixed Temperature Heat Detector

Short Description:


Product Detail

Product Tags

FEATURE

0altbk

▪ Advanced single-chip microcomputer technology

▪ Non-polarized two-wire

▪ Thermal sensitive element improves the response speed of temperature variation

DETAILS

1. Fix the base with two tapping screws, and then connect loop to terminals (polarity-insensitive). After the base is fixed firmly, rotate the bottom of detector and base clockwise, and then the detector will be fitted to the base.

2. Wiring instructions: RVS twisted pair with cross-sectional area≥1.0mm² should be selected for the second bus of the detector, which should be laid through metal pipe or flame retardant pipe. The length of the connecting wire should be limited to the single bus resistance≤ 20Ω, otherwise the wire diameter should be increased.

EN54-5 CERTIFIED

2.1rz

Specifications

TECHNICAL SPECIFICATIONS

Operating Voltage

Loop 24V(18.5V~26V)

Operating Current

Standby current:≤0.3mA;Alarm current:≤0.8mA About 110g

Code range

1~255

Coding method

Electronically coding

Dimension

100mm×51mm(with base)

Mounting hole distance

60mm

Operating environment

Temperature:-10℃~+55℃, Relative Humidity:≤95% non-condensing

Ingress protection rating

IP33

Material and color of enclosure

ABS;Milky white

Maximum transmission distance

1000m


  • Previous:
  • Next:

  • Write your message here and send it to us