LX-MK5263 Addressable Single I/O Module
FEATURE
▪ Line detection function for input and output
▪ Input terminal is ste as normal open detecting function connected with passive contalt
▪ Non-polarized two-wire
▪ Active and passive output
DETAILS
Feedback input terminal has disconnection detection function, add a 10K terminal resistance at one end, otherwise it will report as product feedback terminal
fault. Output line has disconnection and short line detection function, when module does no action, voltage between DC13V to 48V is required at normal open output terminal otherwise it will report as module output line fault.
Open installation applied for the module. Insert mode for installation between base and module. When installing, pull down the module, lead the wire through wiring hole, connect it with terminal and push the module onto the base. The mounting hole distance is 60mm.
EN54-18 CERTIFIED
Specifications
|
TECHNICAL SPECIFICATIONS |
|
|
Operating voltage |
Loop:24V(18.5V~26V);Power:DC24V(DC19V~DC28V) |
|
Standby current |
Loop:≤0.2mA;Power:≤2mA |
|
Starting current |
Loop:≤2mA;Power:≤22mA |
|
Operaing Environment |
Temperature:-10℃~+55℃; Relative Humidity:≤95% non-condensing |
|
Output capacity |
Passive:Capacity:DC30V/3A;Contact resistance in normal condition:100kΩ;Closed when activated;Suitable for DC or AC12V~48V;Active output:DC24V/1.5A |
|
Coding method |
Electronically coding |
|
Code range |
1~255 |
|
Weight |
About 147g(with base) |
|
Material and color of enclosure |
ABS; Porcelain white |
|
Mounting hole distance |
60mm |
|
Dimension(L×W×H) |
86mm×38mm×86mm(with base) |